Catalog pricing shown. Please Sign In to see your pricing.

TPLP527LES2BR6

TPLP527LES2BR6
Unit cooler, walk-in, electric defrost, low profile, 6 FPI, pre-assembled, PSC motors, R404A, 27000 BTUH -20°F, 208-230/1/60 volt
Please note an alternative model exists for this Part Number. Please see the Supersedes tab.
Vendor Name:
Trenton Refrigeration Products
URI Part Number:
TPLP527LES2BR6
Vendor Part Number:
TPLP527LES2BR6
Depth (In.):
15
Width (In.):
94 1/4
Height (In.):
15 7/8
Shipping Weight (Lbs.):
178
Application:
Low Temp
CFM:
4500
Connection Size Inlet (In.):
7/8
Connection Suction (In.):
1 3/8
Connection Type:
ODS
Heater Amps:
19.1
Heater MCA:
23.9
Heater Watts:
4400
Motor Type:
PSC
Number of Motors:
5
Voltage:
208-240/1
Prop65:
WARNING: This product can expose you to chemicals including Lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Standard Features

  • Modern look
  • High efficiency and high strength fan guard
  • Front access
  • Higher capacity
  • Compact
  • Internally enhanced tubing
  • More uniform air flow
  • Convenient mounting brackets
  • Ample electrical and header compartments
  • B(R)* models use PSC motors
  • B(R)*-EC2 models use electronically commutated motors with SmartSpeed® which meet FEISA Act HR6 (2007)
  • Proven motor/fan/motor mount design
  • Liquid line solenoid valve wire harness factory installed
  • Schrader valve on suction header extension outside the cabinet
  • Positive slope, hinged drain pan, central drain connections (approximate)
  • Universal drain fitting
  • Large 3/4" ID (3/4" MPT) drain hole
  • Factory installed distributor nozzle
  • 460/1/60 PSC motor only

Optional Features

  • Wire fan guard
  • SmartSpeed® Technology (Patent Pending) for EC motors
  • Compatibility with SmartVap™ Electronically Controlled System
  • Heresite coating
  • Copper or GW aluminum “Gold Coat” Fins
  • Wire fan guard
  • Painted cabinet

Smart Speed

SmartSpeed® motors consume 60 watts/motor on cycle but only 13 watts/motor during the off cycle and offer an average of 28% savings over single speed ECM motors. Standard on all low profile TLP, TPLP models with electronically commutated motors



  • Lower heater wattage
    Capacities rated using
    • BR2: R407A with 10°F T.D. and 100°F liquid temperature.
    • BR6: R404A with 10°F T.D. and 100°F liquid temperature.
  • Pre-assembled, Pre-engineered in stock option packages. The expansion valve, solenoid valve and thermostat are mounted, wired. Just braze your connecting lines, wire up your electrical connections and you're ready to go. Available R404A (TPLP*BR6) for medium temperature and low temperature electric defrost models
Replacement Parts Supersedes Documents