Catalog pricing shown. Please Sign In to see your pricing.

TVD071M8HT3BB

TVD071M8HT3BB
Call To Order
Condensing Unit, Air Cooled, Outdoor, Medium temp, Bitzer Compressor, Large Vertical Semi Hermetic, R407A, R448A, R449A, R407C, R404A, R507, 71 (2x35) HP, 208-230/3/60, w/ receiver
Vendor Name:
Trenton Refrigeration Products
URI Part Number:
TVD071M8HT3BB
Vendor Part Number:
TVD071M8-HT3B-B
Length (In.):
277 3/8
Width (In.):
86 3/4
Height (In.):
55
Shipping Weight (Lbs.):
6535
Application:
Medium Temp
Compressor:
Bitzer
Connection Liquid (In.):
1 1/8
Connection Suction (In.):
2 1/8
Horsepower:
71 (2x35)
Maximum Fuse / Breaker Size (Amps):
450
MCA (Amps):
344.175
Oil:
Polyol Ester
Receiver Capacity 90 % Full (Lbs.):
254
Receiver Included:
Yes
Refrigerant:
R407A, R448A, R449A, R407C, R404A, R507
Voltage:
208-230/3/60
Prop65:
WARNING: This product can expose you to chemicals including Lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Compatible with Low GWP Refrigerants
  • Units are CULUS Listed.
  • Designed for use with various popular refrigerants.
  • Energy efficient compressors with POE oil. Several options to choose from: Copeland Discus, Bitzer reciprocating.
  • Single, dual and parallel-piped (optional) compressor configurations available.
  • ThermospanTM condenser core design eliminates tube sheet leaks and provides reliable operation.
  • 3/8" condenser tubes reduces refrigerant charge.
  • Generously sized condenser allows unit to operate at higher than normal ambient conditions.
  • Optional coating and fin surfaces for condenser core protection available.
  • Specially designed, thermally protected and permanently lubricated ball bearing condenser fan motor(s).
  • Receivers (where used) are liberally sized and include inlet as well as outlet service valves.
  • Subcooling circuit in condenser on all models (except H8 models) increases overall system efficiency and provides dependable compressor operation.
  • Utilizes pre-formed internal piping, eliminates welded joints and reduces chances of a leak.
  • Electrical components are housed in a spacious and conveniently located panel. In case of a compressor trip, (except on air conditioning models) a Lock-out relay de-energizes the liquid line solenoid valve. In addition, SPDT contact is provided for field wired alarm circuit.
  • End compartment panels allow unrestricted access to service the compressor(s) and all other components.
  • Raceway for pressure control wiring and connections provides neat appearance.
  • Units are available with energy efficient ThermosaverTM hot gas defrost option.
  • Units are environmentally friendly operating on less power and refrigerant charge.

Standard features include:

  • Spring mount compressor with discharge vibration eliminator
  • Compressor head cooling fans on low temperature models (except L8 units)
  • Compressor crankcase heater
  • Flexible hose on all compressor pressure control connections
  • Two valve adjustable (pre-set at factory)
  • Low Ambient head pressure control
  • Condenser fan cycling control (pressure) on two-fan models and up
  • Fused condenser fan motors
  • Receiver inlet/outlet valves and safety pressure relief valve
  • Replaceable liquid line drier & sight glass
  • Anti-short cycle time delay relay
  • Oil failure control (non-electronic)
  • Separate HP and LP compressor controls
  • Part-winding start on all 30 HP and up, operating on 208/230V-3Ph
  • Lock out relay
  • Sub-cooling circuit on medium and low temperature units
  • Electronic liquid injection on L8 units


  • Receiver capacity per circuit, R404A
  • See Document Tab on URI.com for AWEF-compliant applications and capacities