Condensing unit, air cooled, semi-hermetic compressor, low temp, R22, R404A, R507, 30 HP, 208-230/3/60, w/ receiver
Motor Freight
Engineered Items
Vendor Name:
Bohn
URI Part Number:
BLV3000L6C
Length (In.):
170.7
Width (In.):
44 1/2
Height (In.):
55 1/2
Shipping Weight (Lbs.):
2170
Application:
Low Temp
Compressor:
6DT3A300ETSK
Compressor New:
6DT3F11METSK
Connection Liquid (In.):
1 1/8
Connection Suction (In.):
2 1/8
Connection Type:
ODS
Horsepower:
30
MCA (Amps):
121
Oil:
Polyol Ester
Receiver Capacity 90 % Full (Lbs.):
142 (R22) 123 (R404A)
Receiver Included:
Yes
Refrigerant:
R404A, R507A, R407A, R407C, R407F, R448A, R449A
Voltage:
208-240/3
The BV outdoor Discus condensing unit features a new leak resistant design which includes:
The patented fully floating tube condenser coil. Refrigerant carrying copper tubes do not contact any meta support sheets; instead, the coil is constructed with expanded anchor tubes which support the coil construction and do not carry refrigerant. The coil design eliminates one of the major causes of leaks in refrigeration systems.
Limited five year warranty against condenser tube sheet and center support leaks
Prebent copper tubes minimize welded joints on internal piping
All sweat type connections, no flare joints to leak
Fixed high pressure switch eliminates capillary tubes
Standard Features
High efficiency Copeland Discus compressors with POE oil
Thermally protected permanently lubricated ball bearing condenser fan motor(s)
Electrical controls including compressor contactor and optional defrost control are located in easily accessible control box with a hinged cover
Receivers are sized for sufficient pumpdown capacity with inlet and outlet service valves
Cabinet is constructed from prepainted galvanized steel
Convenient access panels for easy servicing to internal components
Suction and discharge vibration eliminators
Separate subcooling circuit in condenser for added capacity and vapor free liquid
Liquid line filter drier and sight glass
Pressure relief valve on receiver
Crankcase heater
Limitizer® (BLV) head pressure control system
Optional Bohnmizer® (BBV) head pressure control system available for energy efficiency and lower refrigerant costs
Receiver capacity for R404A. For R22 multiply by 1.14