Catalog pricing shown. Please Sign In to see your pricing.

RM7840M1017

RM7840M1017
Programmer burner relay module no display, auto, 60 hz, replaces R4140M
Vendor Name:
Honeywell
URI Part Number:
RM7840M1017
Vendor Part Number:
RM7840M1017
Description:
Relay Module, No Display
Shipping Weight (Lbs.):
2.8
Hertz:
60
Initiate Time (Sec.):
10
Main Flame Establishing Period:
10 sec. or Intermittent
Pilot Flame Establishing Period:
4 or 10 sec.
Post Purge (Sec.):
15
Purge:
PURGE will be determined by which ST7800A Purge Timer Card is selected.
Replaces:
R4140M
Run:
STANDBY and RUN can be an infinite time period.
Standby Time:
STANDBY and RUN can be an infinite time period.
Prop65:
No

Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls.

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble-shooting.
  • Only available in NJ / Eastern-Southern NY. Call 914-592-5555 to order.