Catalog pricing shown. Please Sign In to see your pricing.

RM7800M1011

RM7800M1011
Contact your local branch to order.
Programmer burner control with display, auto, 60 hz, replaces BC7000L, PM720M
Vendor Name:
Honeywell
URI Part Number:
RM7800M1011
Vendor Part Number:
RM7800M1011
Description:
Control w/Display
Shipping Weight (Lbs.):
3.00
Hertz:
60
Initiate Time (Sec.):
10
Pilot Flame Establishing Period:
4 or 10 sec.
Post Purge (Sec.):
15
Purge:
PURGE will be determined by which ST7800A Purge Timer Card is selected.
Replaces:
BC7000L; PM720M
Run:
STANDBY and RUN can be an infinite time period.
Standby Time:
STANDBY and RUN can be an infinite time period.
Prop65:
No

Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls.

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble-shooting.
  • Only available in NJ / Eastern-Southern NY. Call 914-592-5555 to order.
Documents