Catalog pricing shown. Please Sign In to see your pricing.

R7140M1007

R7140M1007
Programmer burner control, auto, interrupted pilot, replaces BC7000L, PM720L
Vendor Name:
Honeywell
URI Part Number:
R7140M1007
Vendor Part Number:
R7140M1007
Shipping Weight (Lbs.):
3.95
Main Flame Establishing Period:
10 sec. or intermittent
Pilot Flame Establishing Period:
4 or 10 sec.
Pilot Type:
Interrupted
Post Purge (Sec.):
15
Replaces:
BC7000L; PM720L
Prop65:
No

Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls.
Uses existing subbase for easier installation

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble-shooting.
  • Requires ST7800 purge timer and appropriate R787xx amplifier to complete the replacement
  • Purge time determined by card selected