Catalog pricing shown. Please Sign In to see your pricing.

RA890G1260

RA890G1260
Call To Order
Protectorelay™ primary control, commercial, UV intermittent, 15 sec safety switch, 3.0 flame failure response
Vendor Name:
Honeywell
URI Part Number:
RA890G1260
Vendor Part Number:
RA890G1260
Shipping Weight (Lbs.):
3
Flame Failure Response (sec.):
3.0
Safety Timing (sec):
15
Supply Voltage:
120
Prop65:
No

Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners.

  • Designed for interrupted ignition with intermittent pilot on gas burners, and interrupted or intermittent ignition on oil burners.
  • Use with a C7027, C7035 or C7044 minipeeper ultraviolet flame detector for flame sensing.
  • Relights once after flame failure in attempt to re-establish pilot before lockout.
Documents